Protego BE/HK-E-IIB3 Deflagration Flame Arrester, Endurance Burning Proof, End Of Line, ATEX
Function and Description
The PROTEGO BE/HK-E end-of-line deflagration flame arrester was specifically developed for vessels which are not pressurized and store Ethanol or other alcohols. The combustion of alcohol requires a modified flame arrester element design to provide protection against endurance burning. In addition, the device provides protection against atmospheric deflagration. It is typically installed on in - breathing and out-breathing vent lines to prevent flame transmission into the vessel or plant caused by endurance burning or atmospheric deflagration.
The PROTEGO BE/HK-E consists of the housing (1), a weather hood (2), and the PROTEGO flame arrester unit (3). During normal operation, the metal weather hood is in a closed position. If a stabilized flame burns on the flame arrester element surface, the melting element (5), located in a center position, will melt, and the spring-loaded weather hood will open. The PROTEGO flame arrester unit consists of two FLAMEFILTER discs (4) which are installed in a FLAMEFILTER® casing. The PROTEGO BE/HK-E end-of-line deflagration flame arrester is available for alcohols and other substances with MESG ≥ 0,85mm.
The standard design can be used for operating temperatures up 2 to +60°C / 140°F.
EU conformity according to the currently valid ATEX directive. 3 Approvals according to other national/international regulations on request.
Special Features and Advantages
• Endurance burning protection for alcohols and hydrocarbons with MESG ≥ 0,85mm.
• Weather hood protects the PROTEGO® flame arrester unit against environmental impact, such as nesting animals and weather conditions.
• In case of fire, the weather hood opens, allowing the flame to be seen from a far distance.
• Centrally aligned melting element is resistant to chemicals.
• Modular design enables replacement of individual FLAME- FILTER discs.
• Trouble-free maintenance.
• Provides protection against atmospheric deflagrations and endurance burning b 4 1 Function and Description.
• Cost-effective spare parts.
Design Types And Specifications
There are two different designs:
BE/HK-E- End of line deflagration flame arrester, basic design.
BE/HK-E-H End of line deflagration flame arrester with heating jacket.
Dimensions | DN | 20/ 3/4" | 25/ 1" | 32/ 1/4" | 40/ 1 1/2" | 50/ 2" | 65/ 2 1/2" | 80/ 3" |
| a | 163/ 6.42 | 163/ 6.42 | 163/ 6./42 | 183/ 7.20 | 183/ 7.20 | 218/ 8.58 | 218/ 8.58 |
| b | 180/ 7.09 | 177/ 6.97 | 177/ 6.97 | 190/ 7.48 | 190/ 7.48 | 200/ 7.87 | 200/ 7.87 |
Dimensions in mm/ inches
*To select the nominal size (DN) refer to the flow capacity charts.
Selection of Explosion Group| MESG | Expl. Gr. (IEC/CEN) | Gas Group (NEC) | Special approvals upon request |
| ≥ 0.85 mm | IIB1 | - |
Material Selection for Housing| Design | B | C | Special materials upon request |
| Housing | Steel | Stainless Steel |
| Weather hood | Steel | Stainless Steel |
| Flame arrester unit | A | A, B |
Material Combinations of Flame Arrester Unit| Design | A | C | Special materials upon request |
| FLAMEFILTER casing | Stainless Steel | Stainless Steel |
| FLAMEFILTER casing | Stainless Steel | Hastelloy |
| Spacer | Stainless Steel | Hastelloy |
Flange Connection Type| EN 1092-1; Form B1 | Other types upon request |
| ASME B16.5 CL 150 R.F |